China YASKAWA Fan & Pump Drives Z1000 Drive Manufacturers, Products

The Z1000 frequency converter is designed for building automation applications and is suitable for equipment with power up to 500 horsepower, such as fans, pumps, and cooling towers. The Z1000 features an easy-to-read LCD keypad, a manual/automatic switching interface, and a real-time clock. These features make the Z1000 ideal for a wide range of building automation applications requiring reliable motor control.

Product Description

The Z1000 is a variable-speed drive specifically tailored for HVAC and building automation scenarios, mainly used to control equipment like fans, pumps, and cooling towers. It has the advantages of reliable performance, convenient operation, and strong compatibility, and its power range can fully meet the needs of medium and large-scale building equipment. The following is a detailed overview based on official technical information:

Intelligent Control & Operation

It is equipped with a 5-line 16-character alphanumeric LCD keypad, supporting 7 languages and a copy function. The operation interface is user-friendly. It also has a hand-off-auto interface, which is convenient for manual, automatic and stop control switching. The built-in real-time clock can record the time and date of events, and realize automatic start-stop and speed adjustment without external control components. In addition, the PI control function can maintain the set value of pressure, flow or temperature for closed-loop control of fans and pumps.

Strong Anti-Interference & Stability

It has a built-in EMI/RFI filter that complies with IEC 61800-3 restricted distribution standards for the first environment, effectively reducing electromagnetic interference. At the same time, it is equipped with a 5% line impedance to reduce input harmonics, ensuring the stable operation of the drive and the surrounding electrical equipment. It also has multiple protection functions such as motor protection and momentary power failure ride-through to avoid equipment damage due to abnormal working conditions.

Easy Integration & Expansion

It has embedded BTL-certified BACnet communication, and is also compatible with Modbus/Memo bus, Metasys and Apogee FLN communication protocols, which can be seamlessly connected to building automation systems (BAS). The keypad supports remote installation through the RJ-45 port. Optional remote operation kits are available, and cables of 3-foot and 10-foot lengths are provided to meet the needs of different installation layouts. It also has pre-configured application macros, which can be quickly set up according to specific scenarios such as fans and pumps, saving commissioning time.

Practical Structural Design

The drive is equipped with a sealed radiator, which can be installed in a NEMA 12 enclosure with the radiator exposed, which helps to improve heat dissipation efficiency and prolong the service life of the equipment. The overall structure is compact, and the configured package also reserves space for reactors, fuses, circuit breakers and other common accessories, facilitating later function expansion.

Typical Application Scenarios

The drive is mainly oriented to building automation fields. Its typical application scenarios include central air-conditioning system fans, water circulation pumps in buildings, cooling towers of industrial and commercial buildings, and ventilation and exhaust fans in large public places. It can also be used in other occasions that need to precisely control fluid flow and air volume and pursue energy-saving operation. In addition, its matching Z1000 bypass package has an intelligent bypass and advanced building automation system interface, which is more suitable for scenarios with high requirements for continuous operation of equipment such as hospitals and data centers.

Compliance & Reliability Certification

The product complies with ROHS standards and uses environmentally friendly materials. It has obtained plenum certification (UL 1995) and seismic certification (IBC 2006 - certification 12/2011). The matching Z1000 bypass package is also BTL certified, which meets the relevant safety and quality standards of the global building automation industry and can be safely used in various international markets.

Item Specification
Overload Capacity 110% for 60 seconds, 175% instantaneous
Output Frequency 0.01 to 240 Hz
Control Methods V/Hz Control
Open Loop Vector Control for Permanent Magnet motors
Motor Types Squirrel Cage Induction Type
Interior Permanent Magnet (IPM)
Enclosures NEMA Type 1 / IP20 : 3 - 100 HP 208V and 3 - 250 HP 480V
Open Type / IP00 : 125 - 150 HP 208V and 300 - 500 HP 480V
Ambient Operating Temperature -10°C to 40°C (14°F to 104°F)
Global Certification UL, CSA, RoHS
Standard I/O Multi-Function Programmable Digital Inputs (24VDC): 7
Multi-Function Programmable Analog Inputs (0-10VDC or 4-20mA): 2
Fault Relay Output (Form C - 2 Amps at 250VAC max): 1
Multi-Function Programmable Relay Output (Form A - 2 Amps @ 250VAC max): 3
Multi-Function Programmable Analog Outputs (0-10VDC or 4-20mA): 2
24 Vdc, 150 mA Transducer or Transmitter Power Supply for customer use: 1
Network Communications Built-in:
BACnet, RS485/422 - Programmable up to 76.8 kbps
Optional:
LonWorks, Metasys / APOGEE FLN
Drive Model Number Nominal HP Physical Dimensions (in.) Standard Enclosure
H W D Weight (lbs.)
CIMR-ZU2A0011FAA 3 14.06 4.88 8.58 12.3 NEMA 1
CIMR-ZU2A0017FAA 5 13
CIMR-ZU2A0024FAA 7.5 17.6 4.88 9.17 16.3 NEMA 1
CIMR-ZU2A0031FAA 10 17.2
CIMR-ZU2A0046FAA 15 20.08 7.87 9.35 26.5 NEMA 1
CIMR-ZU2A0059FAA 20 28.7
CIMR-ZU2A0075FAA 25 21.33 10.04 10.37 59.5 NEMA 1
CIMR-ZU2A0088FAA 30 61.7
CIMR-ZU2A0114FAA 40 63.9
CIMR-ZU2A0143FAA 50 30.47 13.39 15.75 143.3 NEMA 1
CIMR-ZU2A0169FAA 60 149.9
CIMR-ZU2A0211FAA 75 154.3
CIMR-ZU2A0273FAA 100 160.9
CIMR-ZU2A0343AAA 125 31.5 19.69 13.78 216.1 Protected Chassis
CIMR-ZU2A0396AAA 150 218.3

Delivery information typically includes delivery times, shipping methods, packaging, etc., which may vary depending on the seller and the location of purchase.

FD-615MT Specs.pdf

Fan & Pump Drives Z1000 Drive Tech & manual.pdf

Download

Frequently Asked Questions (FAQ)

What are the main application scenarios for the Z1000 drive?
The drive is primarily designed for building automation fields. Typical scenarios include central air-conditioning system fans, water circulation pumps, cooling towers, and ventilation/exhaust fans in large public places.
Which communication protocols are compatible with the Z1000?
It features embedded BTL-certified BACnet communication and is also compatible with Modbus/Memobus, Metasys, and Apogee FLN protocols for seamless integration with Building Automation Systems (BAS).
What certifications and compliance standards does the Z1000 meet?
The Z1000 complies with RoHS standards and has obtained plenum certification (UL 1995) and seismic certification (IBC 2006). Its bypass package is also BTL certified.
What is the overload capacity of this variable-speed drive?
The drive features an overload capacity rated at 110% for 60 seconds and 175% instantaneous overload protection.
What motor types are supported by the Z1000 drive?
It supports control for Squirrel Cage Induction Type motors and Interior Permanent Magnet (IPM) motors.
Does it feature built-in filters to reduce electrical interference?
Yes, it has a built-in EMI/RFI filter that complies with IEC 61800-3 restricted distribution standards, and includes 5% line impedance to reduce input harmonics.

Related Products