| Product Type | Current measuring transducer |
| Insulation characteristics | |
| Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
| Overvoltage category | III (300 V) |
| Pollution degree | 2 |
| Width | 22.6 mm |
| Height | 106.7 mm |
| Depth | 113.8 mm |
| Depth (DIN rail mounting) | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
| Circular conductor | |
| Diameter | 11 mm |
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Housing material | PA 6.6-FR |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 60 °C (-40 °F ... 140 °F) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 m |
| Permissible humidity | ≤ 95 % (non-condensing) (operation) |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section AWG | 24 ... 13 |
| Standards/regulations | IEC 61010-1 / IEC/EN 61131-2 (type 3) |
| Item number | 1136513 |
| Packing unit | 1 pc |
| Weight per piece (including packing) | 141.2 g |
| Customs tariff number | 85437090 |
| Country of origin | DE |
| Item number | 1136513 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Weight per piece (including packing) | 141.2 g |
| Weight per piece (excluding packing) | 141.2 g |
| Customs tariff number | 85437090 |
| Country of origin | DE |
Q1: What types of current signals can the ECM-UC-100A-UI measure?
A1: It is designed to measure AC, DC, and distorted current signals across a measurement range of 0 A to 125 A, preventing monitoring deviations caused by abnormal waveforms.
Q2: How is the device configured?
A2: The device can be configured without an external 24 V DC power supply. You simply connect it to a device via a USB-C interface and use its built-in web server for parameter adjustments, eliminating the need for dedicated software.
Q3: What kind of wiring technology does this transmitter support?
A3: It utilizes a tool-free push-in connection design. This allows for rapid securing of conductors, improving installation efficiency and minimizing potential contact issues.
Q4: What is the operating temperature range for the ECM-UC-100A-UI?
A4: The transmitter functions reliably in ambient operating temperatures ranging from -40 °C to 60 °C (-40 °F to 140 °F).
Q5: What are the physical dimensions and mounting requirements?
A5: It measures 22.6 mm in width, 106.7 mm in height, and 113.8 mm in depth. It is designed to snap easily onto standard DIN rails (NS 35/7,5 in accordance with EN 60715).
Q6: What standards and protection ratings does this device meet?
A6: The transmitter has an IP20 degree of protection, features safe isolation in accordance with IEC/EN 61010-1 standards, and has a V0 flammability housing rating according to UL 94.